Parker Transair 2019

92 1 2 3 4 Practical Examples TRANSAIR ® QUICK ASSEMBLY BRACKETS FITTING A BRACKET TO A PRESSURISED SYSTEM TOOLS REQUIRED PROCEDURE 1 - Position the pressurised system bracket and tighten with the recommended tightening torque. 2 - Screw the drilling tool onto the ball valve. Drill fully. 3 - Remove the drill and close the ball valve immediately. 4 - Dismantle the drilling tool. 5 - Empty the chips between each drilling. Under pressure bracket with 1/2" ball valve Ø25: EA98 06 01 tightening torque 8-12 N.m Ø40: EA98 40 04 tightening torque 8-12 N.m Ø50: EA98 50 04 tightening torque 5-10 N.m Ø63: EA98 63 04 tightening torque 5-10 N.m Use the under pressure drilling tool (EA98 06 00) to fit a bracket to an existing pressurised system. This can be simply done with use of a standard drill. Drill bit Threaded connector to screw onto the air intake Silencer attachment point Tool body End cap