Parker Transair 2019

107 L1 L1 H L2 H L2 L3 L3 H Expansion / Contraction In order to compensate for the effects of expansion and contraction due to variations in temperature, any fluctuations in the length of the Transair ® aluminium pipe network should be calculated. L: length of Transair ® straight line to be installed (in m) T: variation between temperature when installing and maximum operating temperature (in C°) L: line length variation (in mm) For Transair ® Ø-16.5 - Ø25 - Ø40 - Ø50- Ø63 - Ø76 - Ø100 - Ø168 aluminium pipe networks: L = (a x L) + (0.024 x L x T) 1 - Expansion related to pipe retraction in the connector 2 - Expansion related to temperature variations DIRECTION CHANGE USING AN ELBOW USING A QUICK ASSEMBLY BRACKET 1 2 • For Transair ® aluminium pipe networks Ø16.5 - Ø25 - Ø40 - Ø50 - Ø63 L1 = H x 20 H in m, L1 in mm • For Transair ® aluminium pipe networks Ø76 - Ø100 - Ø168 L1 = H x 13.33 • For Transair ® aluminium pipe networks Ø16.5 - Ø25 - Ø40 - Ø50 - Ø63 L2 = H x 8.67 L3 = H x 8.67 H in m, L2 and L3 in mm EXPANSION CALCULATION Ø16.5 Ø25 Ø40 Ø50 Ø63 Ø76 Ø100 Ø168 Pipe 3m a=0.06 a=0.20 a=0.40 a=0.68 a=0.68 a=1.0 a=1.0 a=1.34 Pipe 6m (4.5m for Ø16.5) a=0.045 a=0.10 a=0.20 a=0.34 a=0.34 a=0.50 a=0.50 a=0.67 Installation Guide

RkJQdWJsaXNoZXIy MzYzNzg=