General Catalogue Solenoid Valves for Fluid Control

465 Parker Hannifin Corporation Fluid Control Solutions Europe General Catalogue FCSE/0112/UK V2.2 07/2022 EXPLOSION PROOF ELECTRICAL PARTS ZONE 1/21 To Order a Coil choose Coil Ref + Voltage Code, example: 492190 for 24 VDC = 492190C2 2.0/2.1 COIL GROUP 492190 - ELECTRICAL PARTS 50 mm This coil can be mounted with every Parker ATEX solenoid valves corresponding to the specified Coil Group. See column "Coil Group" within valve pages. Application: Control of solenoid valves in dangerous areas where explosion-proof protection Ex eb mb IIC T3 to T4 is required. Benefits: Rotatable 360°, fiberglass -reinforced plastic housing. Solenoid coil, rectifier (silicium diodes), fuses and varistor protection are completely encapsulated into the coil housing by epoxy resin for shock and corrosion protection. Small size for ease of mounting in confined space. Reference 492190 Certificate LCIE 02 ATEX 6023 X - IECEx LCI 06.0011 X Coil Group 2.0 / 2.1 Type of protection Gas II 2 G - Ex eb mb IIC T3 / T4 Dust II 2 D - Ex tb IIIC - 195°C / 130°C Degree of protection IP66 according to IEC/EN 60529 Standards Ambient temperature -40°C to +75°C / +40°C The operating temperature of the valve/coil can be limited by that of the valve Insulation Class H 180°C Electrical connection Connection box with terminals and cable entry via gland M20 x 1.5 Possibility for additional earth via external screw Electrical consumption DC Pn (hot) 9 W P (cold) 20°C 11 W AC Pn (holding) 11 W Attraction cold 13 W Weight 320 g Voltages "Un" VAC/Hz Code VDC Code -10% to +10% of the Un 24/50-60 110/50-60 230/50-60 P0 P2 P9 24 48 110 C2 C4 C5 INCREASED SAFETY AND ENCAPSULATED ELECTRICAL PARTS "eb mb"

RkJQdWJsaXNoZXIy MzYzNzg=