94 www.parker.com/gsfe Thermal and Power Management Hypercool Air Cooled Aftercoolers Technical Data - Hypercool Water Cooled Model Flow Rate Maximum Operating Pressure Pipe Connections m³/h m³/min bar g psi g Air Water Standard Version WFN050 3000 50 12 174 DN125 1 " WFN090 5400 90 12 174 DN200 1 " Removable Tube-Bundle WRN007 420 7 16 232 DN 50 " WRN016 960 16 16 232 DN 80 " WRN028 1680 28 12 174 DN 100 1" WRN050 3000 50 12 174 DN 125 1 " WRN090 5400 90 12 174 DN 200 1 " WRN130 7800 130 10 145 DN 250 1 " WRN170 10200 170 10 145 DN 300 2" WRN250 15000 250 10 145 DN 350 DN 65 WRN350 21000 350 10 145 DN 450 DN 80 WRN450 27000 450 10 145 DN 500 DN 100 WRN550 33000 550 10 145 DN 600 DN 100 Performances refer to clean cooler conditions with air at FAD 20°C / 1 bar A, and at the following working conditions: air suction 25°C / 60% RH, 7 bar g working pressure, 120°C compressed air inlet temperature, temperature approach between air outlet and water inlet of ca. 10°C. Maximum air inlet temperature: 200°C (for higher temperatures and other gases contact Parker Sales Companies).
RkJQdWJsaXNoZXIy MTQ4NTgyMQ==